35

Battery calculation worksheet

Supervisory (AUX1, AUX2, AUX3, AUX4)
Note: Only add auxiliary current if SW2-7 is OFF. Auxiliary output stays on
after AC power failure.

Device type

Quantity

Current (mA)

Total/device

Total AUX current (0 if switch SW2-7 is off, maximum 6.5 A
for BPS6A and 8 A for BPS10A):

mA

(A)

Number of circuits set to
AUX

35 mA (per AUX
circuit)

mA

(B)

200 mA AUX

Device type

Quantity

Current (mA)

Total/device

Total 200 mA AUX current:

mA (C)

Rated base BPS supervisory current:

70 mA (D)

Total supervisory current (A + B + C + D):

mA (E)

Hours of supervisory:

Hrs (F)

Supervisory mAh (E x F):

mAh (G)

Alarm (NAC1, NAC2, NAC3, NAC4)

Device type

Quantity

DC current (mA,
RMS)

Total/device

Total NAC current:

mA (H)

Rated base BPS alarm current:

270 mA (J)

Total alarm current (E + H + J):

mA (K)

Minutes of alarm:

Min (L)

Hours of alarm (L/60):

Hr (M)

Advertising