Nac class a wiring – Edwards Signaling EBPS Remote Booster Power Supply User Manual

Page 31

Advertising
background image

Remote Booster Power Supply Technical Reference Manual

25

NAC Class A wiring

Connect one NAC circuit to one NAC output, either NAC1 or NAC3. Terminate
the circuit at the NAC2 or NAC4 terminal screw, respectively.

Figure 14: NAC class A wiring

+

+

+

+

+

+

TB2

TB1

TB

5

(1)

(2)

(3)

(4)

(5)

(6)
(7)
(8)

(9)

(10)

(11)

(12)
(13)
(14)

(17)

(19)

(15)

(16)

(20)

(21)

Legend
(1) NAC1/AUX1
(2)

NAC2/AUX2 (return for NAC1)

(3) NAC3/AUX3
(4)

NAC4/AUX4 (return for NAC3)

(5)

200 mA AUX Continuous

(6) Sense 1 IN
(7) Sense

1

COM

(8) Sense

1

OUT

(9) Sense 2 IN
(10) Sense

2

COM

(11) Sense

2

OUT


(12) Trouble NO
(13) Trouble

COM

(14) Trouble

NC

(15) Notification appliance circuit (NAC)
(16) Notification

appliance circuit (NAC)

(17) Input from signaling circuit
(18) To next booster, or NAC returning to

existing control panel

(19) EOL for IDC circuit
(20) Control circuit source
(21) AC power fail monitoring

Note: The AC power failure panel connection annunciates at the panel but does not report off
premises for a predetermined time in US fire applications. See Table 8 on page 19.