Remote Booster Power Supply Technical Reference Manual

13

Figure 8: Ground fault enable

(1)

(2)

+

+

(3)

(1) Control panel. The control panel is responsible for ground fault detection when the BPS is

wired in this fashion.

(2) BPS. Disable the BPS’s ground fault jumper (JP3).
(3) To next BPS that requires ground fault detection from the control panel.

JP3

1 2

GF disable: Do not install jumper

GF enable: Install jumper

Battery charging (JP4)

The battery charging jumper is a small wire that controls how the batteries are
charged. Battery size determines whether you must cut the jumper wire or leave
it intact.

JP4

Cut

the jumper wire when using batteries under 10 Ah.

Do not cut

the jumper wire when using batteries 10 Ah or over.