Notification appliance circuit calculations, Introduction, What you’ll need – Edwards Signaling EBPS Remote Booster Power Supply User Manual

Page 43

Advertising
background image

Remote Booster Power Supply Technical Reference Manual

37

Notification appliance circuit calculations

Introduction

This topic shows you how to determine the maximum cable length of a
notification appliance circuit (NAC) for a given number of appliances.

Two methods are presented: worksheet and equation. The worksheet method is
simpler, but your installation must meet the criteria listed on the worksheet. If
your installation does not meet these criteria, you need to use the equation
method.

The methods given here determine cable lengths that work under all operating
conditions. The calculations ensure that the required operating voltage and
current will be supplied to all notification appliances. To do this, we assume these
two worst-case conditions:

• The voltage at the NAC terminals is the minimum provided by the power

supply

• The notification appliances are clustered at the end of the NAC circuit

Other, more detailed methods that distribute the appliance load along the NAC
cable may indicate that longer cable runs are possible.

What you’ll need

Appliance and cable values

Whether you use the worksheet method or the equation method, you’ll need to
know:

• The minimum operating voltage required for the appliances

• The maximum operating current drawn by each appliance

• The resistance per unit length of the wire used (Ω/ft)

This information can be found on the appliance installation sheets and on the
cable specification sheet.

Power supply values

For either method, you’ll need some fixed or calculated operating values for your
specific power supply. The fixed values are:

• Maximum voltage = 26.3 V
• Source voltage = 19.1 V
• Load factor = 0.59 V/A
• Power type = DC (filtered/regulated)

Advertising