Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5)

200 mA AUX Continuous

(6) Sense 1 IN
(7) Sense

1

COM

(8) Sense

1OUT

(9) Sense 2 IN
(10) Sense

2

COM

(11) Sense

2

OUT

(12) Trouble NO
(13) Trouble

COM

(14) Trouble

NC

(15) Notification appliance circuit (NAC)


(16) UL listed EOL 15 kΩ
(17) From existing fire alarm panel

notification circuit or CC1(S) module

(18) Out to EOL or next device
(19) NAC

circuit

(20) UL listed EOL 15 kΩ
(21) Data out to next device
(22) Data in from previous device or

Signature controller

(23) NAC circuit
(24) UL listed EOL 15 kΩ
(25) EOL 15 kΩ, when used as a NAC
(26) UL listed EOL relay
(27) EOL 47 kΩ

Notes

When a booster power supply output is programmed as an AUX output, a listed EOL relay
(PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the AUX output.

When a booster power supply output is programmed as an NAC output, a 15 kΩ EOL resistor
must be used for supervision.