Remote Booster Power Supply Technical Reference Manual

UL 864 programming requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES

This product incorporates field-programmable options. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as
indicated below. Some options were permitted under the previous versions of UL 864 and are

provided to allow for service replacements on those systems.

Programmable feature or
option

Permitted in
UL 864? (Y/N)

Possible settings

Settings permitted
in UL 864

Four second NAC audible
synchronization delay [1]

N

On (4 second delay)
Off (1 second delay)

Off

AC power delay

Y

On (3 hour, no
dedicated AC failure
contact)
Off (no delay)

On