Remote Booster Power Supply Technical Reference Manual

Notes

CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.

Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.

CC1(S) wiring must be within three feet of the BPS enclosure and in conduit or mounted
within the BPS’s enclosure. If CC1(S) wiring is more than three feet from a BPS enclosure,
then a separate listed EOL relay (PAM1, 6254A-003, or 73402A) or equivalent must be used
to supervise the 200 mA AUX circuit wiring.

When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power loss to the control panel. When DIP
switch SW2-6 is OFF, the CT1 module is not required.