Remote Booster Power Supply Technical Reference Manual

15

Setting the DIP switches

Two eight-position DIP switches are used to configure the BPS. The following
sections show the DIP switch settings for the various input and output
configurations.

Note:

As shipped from the factory, all switches are in the OFF position.

Figure 9: Switch settings

SW1

SW2

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

Sense 1 and 2 operation (SW1-1 to 3)

The BPS has three operating modes, as shown in the following table. Switches
SW1-1, -2, and -3 determine which mode is used.

Table 2: Switch settings

Operating mode [1]

SW1-1

SW1-2

SW1-3

Correlate mode

OFF

Genesis Master mode

ON

OFF

ON

Nondelayed mode

ON

ON

[1] See the descriptions below for operation details

These switches also determine how Sense 1 and 2 correlate to the NAC circuits.
Details for each mode are described below.

Correlate mode

In correlate mode, switches SW1-2 and SW1-3 control which NACs activate
when the sense circuits activate. The correlations do not affect output circuits
that are operating as AUX circuits.

The following table details which NACs activate when the sense circuits activate.

Advertising