Remote Booster Power Supply Technical Reference Manual

39

Worksheet method

Use this worksheet to determine the maximum cable length of a notification
appliance circuit for a given number of appliances.

Use this worksheet only if all the appliances are regulated. That is, they must
have a minimum operating voltage of 16 V. For other appliances, use the
“Equation method.”

Worksheet 1: NAC cable length

NAC1 NAC2 NAC3 NAC4

Total operating current [1]

A

Load factor

×

0.59

0.59

0.59

0.59

V/A

Load voltage drop

=

V

Source voltage

19.1

19.1

19.1

19.1

V

Load voltage drop

V

Minimum voltage

=

V

Regulated appliance voltage

16.0

16.0

16.0

16.0

V

Voltage drop [2]

=

V

Total operating current

A

Maximum resistance

=

Wire resistance (Ω/ft) [3]

Maximum wire length

=

ft

2

2

2

2

Maximum cable length

=

ft

[1] Total of the maximum operating currents for all appliances as specified for DC power. See

the appliance installation sheets for operating currents.

[2] This voltage drop is valid for regulated notification appliances only. For special application

appliances, see “Equation method,” later in this topic.

[3] Use the manufacturer’s published wire resistance expressed in ohms per foot. For typical

values, see Table 11 on page 40.