Remote Booster Power Supply Technical Reference Manual

31

Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5)

200 mA AUX Continuous

(6) Sense 1 IN
(7) Sense

1

COM

(8) Sense

1

OUT

(9) Sense 2 IN
(10) Sense

2

COM

(11) Sense

2

OUT


(12) Trouble NO
(13) Trouble

COM

(14) Trouble

NC

(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 kΩ
(17) EOL 47 kΩ
(18) Data in from previous device or

Signature controller

(19) Data out to next device

Notes

CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.

Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.

If CC1(S) wiring is more than three feet from a BPS enclosure, then a separate listed EOL
relay (PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the 200 mA
AUX circuit wiring.

When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power.