Wire routing – Edwards Signaling EBPS Remote Booster Power Supply User Manual

Page 27

Advertising
background image

Remote Booster Power Supply Technical Reference Manual

21

Wire routing

Separate power-limited from nonpower-limited wiring. Wiring within the enclosure
should be routed around the perimeter of the enclosure, not across the circuit
board.

Figure 10: Wire routing

(4)

(4)

(3)

(2)

(1)

Legend
(1) Power-limited wiring area
(2) Route AC supply through knockouts in nonpower-limited area
(3) Battery wiring
(4) Battery

Notes

Maintain 0.25 in. (6 mm) spacing between power-limited and nonpower-limited wiring.

NAC circuits are power-limited and supervised for opens, shorts, and overcurrents. When
configured as auxiliary power circuits, they are power-limited and supervised for shorts and
overcurrents.

Source must be power-limited. Source determines supervision.

Position the battery terminals towards the door.