Ferrite cores are recommended for all applications, Twisted wire, Ms-9600 control panel – Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 17

Advertising
background image

Document #50049 Rev. E0 01/22/01 P/N 50049:E0

17

Panel Mounting

2.2.2 MS-9600

The UDACT-F may be mounted to a BRKT-9600 bracket inside the FACP cabinet (see MS-9600 instruction manual)
or mounted remotely in a UBS-1F or ABS-8RF enclosure (see Figure 2-3) and wired according to the diagram below.

Notes for External Applications:

1.

Ferrite cores are recommended for all applications

2.

Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm

2

) twisted wire

3.

Shielded wire is not required (unless mandated by local AHJ)
If shield wire is used, connect only one end of the shield:

✓ shield may be connected to cabinet (earth ground) at fire alarm panel, or
✓ shield may be connected to TB1 Terminal 5 (shield) at UDACT-F as shown in Figure 2-3. Note that the

shield end that is not connected should be insulated to prevent accidental grounding. Do not connect
both ends of the shield under any circumstance, since a ground fault may result.

4.

Conduit is recommended for external wire runs. Consult local building codes

5.

Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on the UDACT-F to a
solid building earth ground. Conduit alone will not provide a reliable earth ground.

6.

UDACT-F may be located up to 6,000 feet (1,800 m) away from the host control panel

7.

Refer to “Specifications” on page 10, for power requirements

J10

J5

T B 3

J P 3

J P 5

J P 6

J 1 0

J 11

C UT TO
D ISAB LE
LO C A L
C HAR G ER

C UT TO
M O NITO R 4X TM

4XT M O P T BD

T B 4

T B 5

T B 6

T B 7

T B 8

A LA R M T R B L

S UP V

T

X

R

C

V

D

T

R

G

N

D

I

N

+

O

U

T

+

I

N

O

U

T

s hie ld

+ –

+ 24V

G N D

R S +

R S –

S H IE LD

R S +

R S –

1
2
3
4
5
6
7

FIGURE 2-4:

UDACT-F Wiring to MS-9600

24 VDC
Nonresettable
Power

MS-9600 Control Panel

Advertising