Output Circuits

24

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

2.4

Output Circuits

2.4.1 Telephone Circuits

Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. The RJ31X jacks must be ordered separately.

Note that it is critical that the UDACT-F be located as the first device on the incoming telephone circuit to properly
function.

FIGURE 2-9:

Wiring Phone Jacks

Modular Female Connectors

Male Plug Connectors

Primary Phone Line PH-1

Secondary Phone Line PH-2

7 foot

cable

(MCBL-7)

order separately

Note: Shorting bars inside
RJ31X Jack removed during
male plug insertion

Green Wire

Red Wire

Green Wire

Red Wire

Tip

Ring

Ring

Tip

To premises phones

Tip

Ring

To premises phones

Tip

Ring

(Primary Lines)
Incoming Telco
Phone Lines

(Secondary Lines)
Incoming Telco
Phone Lines