Programming Options

32

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

Backup Reporting (57)

Leaving address 57 at '0' means that reports will be transmitted to the secondary phone number only if attempts to
communicate to the primary phone number are unsuccessful. Programming a '1' causes all reports to be transmitted
to the secondary phone number.

Touchtone/Rotary Select (58)

A '0' programmed in this address by the factory triggers Touchtone dialing over both phone lines. Enter '1' for rotary
dialing.

Make/Break Ratio (59)

An entry must be made in this address only if address 58 is set to '1'. Address 59 is factory set to '0' which is a 67/33
ratio, but may be changed to '1' which is 62/38 ratio.

Address (60)

Leave factory default of '0'.

Address (61)

Leave factory default of '0'.

AC Loss Reporting Delay (62)

The factory default entry of '1' causes a 6 hour time delay for AC loss reporting. A '0' entry causes immediate report-
ing of AC loss. Valid entries are '0 to 9' and 'A to F' corresponding to the following reporting delay times:

1 = 6 hours

9 = 17 hours

2 = 7 hours

A = 18 hours

3 = 8 hours

B = 19 hours

4 = 9 hours

C = 20 hours

5 = 10 hours

D = 21 hours

6 = 11 hours

E = 22 hours

7 = 15 hours

F = 23 hours

8 = 16 hours

Host Panel ID (63)

Enter one of the following digits corresponding to the control panel in which the UDACT-F is installed. A correct
entry is essential for proper operation.

0 = MS-9200

5 = MS-9600

1 = Do not use

6 = Do not use

2 = Sensiscan 2000

7 = Do not use

3 = Do not use

8 = Do not use

4 = Do not use

9 = Do not use