background image

Point Assignments - MS-9600

58

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

Appendix F

Point Assignments - MS-9600

(Program Address 56 = 3 or 4)

F.1

Type Mode Programming

To disable or identify a zone or point in Type Mode (refer to “Type Mode” on page 44), the following Entries/
Addresses are used:

F.1.1 For Zone Identification:

Zones 1 - 99 are programmed by Entries/Addresses 01 - 99. The factory default code is 'fire alarm’ (see “Zone
Assignments” on page 64).

F.1.2 For Point Identification:

Loop 1, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 001 - 064
Loop 2, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 065 - 128
Loop 1, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 129 - 192
Loop 2, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 193 - 256
Loop 1, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 257 - 287 (288 not used)
Loop 2, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 289 - 319 (320 not used)
Loop 1, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 321 - 384
Loop 2, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 385 - 448
Loop 1, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 449 - 512
Loop 2, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 513 - 576

F.2

Event Code/Report Transmission

Via Ademco Contact ID Format Only

F.2.1 For Zone Reporting:

Zones 1 - 99 report as zone numbers 01 - 99 (see “Zone Assignments” on page 64).

F.2.2 For Point Reporting:

Loop 1, Modules 1 - 64 report as device numbers 001 - 064
Loop 2, Modules 1 - 64 report as device numbers 065 - 128
Loop 1, Modules 65 - 128 report as device numbers 129 - 192
Loop 2, Modules 65 - 128 report as device numbers 193 - 256
Loop 1, Modules 129 - 159 report as device numbers 257 - 287 (288 is not used)
Loop 2, Modules 129 - 159 report as device numbers 289 - 319 (320 is not used)
Loop 1, Detectors 1 - 64 report as device numbers 321 - 384
Loop 2, Detectors 1 - 64 report as device numbers 385 - 448
Loop 1, Detectors 65 - 128 report as device numbers 449 - 512
Loop 2, Detectors 65 - 128 report as device numbers 513 - 576
Loop 1, Detectors 129 - 159 report as device numbers 577 - 607 (608 is not used)
Loop 2, Detectors 129 - 159 report as device numbers 609 - 639 (640 is not used)