Programming reference sheets – Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 52

Advertising
background image

Programming Reference Sheets

52

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

Appendix C

Programming Reference Sheets

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. Default all Fs

16

Primary Communication Format: Enter 0 - F.

17

18

19

20

Primary Account Code: Valid entries are '0 - F'. Default is '0000'.

21

22

23

24

Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).

25

Primary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. Default all Fs

42

Secondary Communication Format: Enter 0 - F.

43

44

45

46

Secondary Account Code: Valid entries are '0 - F'.

47

48

49

50

Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).

51

Secondary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.

52

53

Start Monitoring Address.

54

55

End Monitoring Address.

56

UDACT-F Communication Selection. Enter '0' to disable UDACT-F communication; '1' for zone reporting

receive only communication; '2' for zone reporting receive/transmit communication; '3' for point reporting receive
only communication; '4' for point reporting receive/transmit communication; '5' for code wheel matching reporting,
receive only; '6' for code wheel matching point reporting, receive/transmit.

57

Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary phone

number receive all reports and messages along with primary phone number.

58

Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.

59

Make/Break Ratio. If rotary dialing is selected in Address 58; enter '0' for a 67/73 make/break ratio; '1' for a

62/38 make/break ratio.

60

Leave default of '0'.

61

Leave default of '0'

62

AC Loss Delay. Enter '0' for no time delay after AC loss; '1' for 6 hours; '2' for 7 hours; '3' for 8 hours; '4' for

9 hours; '5' for 10 hours; '6' for 11 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for
19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours. Default is '0'.

63

Host Panel ID. Enter '0' for MS-9200; ‘2’ for Sensiscan 2000; ‘5’ for MS-9600; all other entries are invalid.

64

65

Loop Number for General Reports. Factory set to '00'.

66

67

68

Sensor Number for General Reports. Factory set to '000'.

...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...

Advertising