Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 26

Advertising
background image

Output Circuits

26

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

FIGURE 2-11:

Monitoring for UDACT-F Trouble

SLC Loop to Fire

Alarm Control Panel

MMF-300 Series
Monitor Module

Wiring in

same room as

UDACT-F

3.9K ohm EOL

resistor

(supplied)

All wiring to relay must be in the same room

within 20 feet of the UDACT-F and in conduit.

MR-101/C

(MR-201/C may also be used)

Earth Grnd

Comm Fail

+24 VDC

UDACT-F

Note: MMF-300 Series Monitor Module is used to supervise Normally Closed output of MR-101/C. On UDACT-F trouble and Comm. Fail, MR-101/
C relay contact will open, causing M300 to transmit trouble condition to the FACP.

Advertising