Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 50

Advertising
background image

Reporting Formats

50

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

Point Reporting

By using the Type Mode feature with address 56 set to 3, 4, 5 or 6, identification of each type of activated device is
possible. Note that addressable detectors report as code 111. It should also be noted that the meaning of the first digit
of the three digit zone/sensor number will depend on the Type Mode programmed in address 56 (i.e. Type 2, Device
address 1 in the tables below, when 5 or 6 is programmed in address 56, C001 will be reported for both modules and
detectors. When 3 or 4 is programmed in address 56, C101 will be reported for modules while C001 will be reported
for detectors). Module points are programmable.

The following table provides examples of reporting structures for addressable modules.

1.

Use of M302 Monitor Module for conventional smoke and duct detectors

2.

99 relates to MS-9200; 159 and 259 relates to MS-9600

The following table provides an example of the reporting structure for addressable smoke detectors.

1.

99 relates to MS-9200; 159 relates to MS-9600

Zone Reporting

By using the Type Mode feature with address 56 set to 1 or 2, identification of the function of each software zone is
possible. The following table provides examples of zone reporting structures.

1.

56 relates to MS-9200; 99 relates to MS-9600

TABLE A-4:

Addressable Module Reporting Structure

Type ID#

Activated Device

Module

Point

Report

Address 56 = 5 or 6

Report

Address 56 = 3 or 4

2

Supervisory Alarm

1

E200 00 C001

E200 00 C101

8

Smoke Zone Alarm

1

(conventional)

2

E111 00 C002

E111 00 C102

3

Pull Station Alarm

3

E115 00 C003

E115 00 C103

4

Heat Sensor Alarm

4

E114 00 C004

E114 00 C104

5

Waterflow Alarm

5

E113 00 C005

E113 00 C105

6

Duct Detector Alarm

1

(conventional)

6

E116 00 C006

E116 00 C106

7

Flame Sensor Alarm

7

E117 00 C007

E117 00 C107

.......................... through ........................

8

Smoke Zone Alarm

1

(conventional)

99 or 159

2

E111 00 C099 or

E111 00 C159

2

E111 00 C199 or

E111 00 C259

2

Type ID

Activated Device

Addressable

Detector Point #

Report

Address 56 = 3, 4, 5 or 6

Automatically set to

smoke detector (8)

300 or 350 Series

Detectors

001 to 099 or 159

1

E111 00 C001 to

E111 00 C099 or E111 00 C159

1

TABLE A-5:

Zone Reporting Structure

Type ID #

Zone Function

Zone #

Report

8

Smoke Zone

1

E111 00 C001

5

Waterflow Zone

2

E113 00 C002

2

Supervisory Zone

3

E200 00 C003

3

Pull Stations

4

E115 00 C004

............... through ...................

5

Waterflow Zone

56 or 99

1

E113 00 C056 or

E113 00 C099

1