Switch (Key) Functions

28

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

3.2

Switch (Key) Functions

The function of each switch (key) in Program Mode is illustrated in Figure 3-1.

3.3

Programming Options

Primary Phone Number (00-15)

The first sixteen addresses are factory set to 'F' (from 00_F to 15_F). Programming is typically done as follows:

✓ If the phone number to be entered is 484-7161, press 4
✓ The display will read 00_4
✓ Press the [ENTER/STORE} key to save the entry to memory and increment to the next address 01_F
✓ Enter the remaining numbers in their respective addresses as shown below:

Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha digits (A - F) representing the following functions:

A = * on a Touchtone phone keypad

B = # on a Touchtone phone keypad

C = look for secondary dial tone for up to two seconds, then dial anyway

D = three second pause

E = five second pause

F = end of phone number (F must be entered)

FIGURE 3-1:

UDACT-F Keypad

No function in Program Mode

Select operating mode

Increment memory address

1st press = First memory address
2nd press = Enter any address

Decrement memory address

Save data, go to next address

Address entry keys are 0 to 9

Data entry keys are 0 to 9 and A to F

4

8

4

7

1

6

1

F

F

F

F

F

F

F

F

F

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15