Operating Instructions

40

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

CHAPTER 4

Operating Instructions

4.1

Normal Mode

The UDACT-F has five modes of operation:

• Normal Mode

• Type Mode

• Program Mode

• Lamp Test Mode

• Troubleshoot Mode

Upon initial power-up, the system will be in Normal Mode. This section describes the operation of the UDACT-F in
the Normal Mode.

4.1.1 Keypad Functions

Clear

The Clear function will cause the UDACT-F to :

• cease transmissions

• clear any active or pending transmissions

• reset and return to normal system processing

To perform the Clear function, press the CLEAR key followed by 2532 and then press the [ENTER/STORE] key.

2532 spells CLEA on a Touch-Tone

®

phone.

Test

If the TEST key is pressed three times in rapid succession, the UDACT-F will transmit a test message to both Central
Stations. The message reported is the same as the automatic test message for all formats except Ademco Contact ID.

Mode

Pressing the MODE key followed by a valid 4-digit numerical code and pressing the [ENTER/STORE] key selects
one of the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then the [ENTER/STORE] key.

6676 spells NORM on a Touch-Tone

®

phone.