Programming Options

38

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

4+2 Standard and 4+2 Express Formats

If '1, A or C' is entered for address 42, the following data is automatically programmed for the Secondary Phone num-
ber event codes. Enter a '0' for the data setting to disable the report.

TABLE 3-6:

Secondary Number Event Codes - 4+2 Standard and 4+2 Express

Address

Description

Setting

139 - 140

Secondary # General Alarm Code

11

141 - 142

Secondary # Zone/Point Alarm Code

00

143 - 144

Secondary # General Supervisory Code

81

145 - 146

Secondary # Zone/Point Supervisory Code

00

147 - 148

Secondary # General Fault Code

F1

149 - 150

Secondary # AC Fault Code

F6

151 - 152

Secondary # Zone/Point Fault Code

00

153 - 154

Secondary # Low Battery Fault Code

F8

155 - 156

Secondary # Telco Primary Line Fault Code

FA

157 - 158

Secondary # Telco Secondary Line Fault Code

FB

159 - 160

Secondary # NAC Fault Code

FC

161 - 162

Secondary # Communication Trouble Primary # Code

FD

163 - 164

Secondary # Communication Trouble Secondary # Code

FE

165 - 166

Secondary # 485 Communication Trouble Code

FE

167 - 168

Secondary # System Off Normal Code

FF

169 - 170

Secondary # UDACT-F Off Normal Code

FF

171 - 172

Secondary # General Alarm Restore Code

E1

173 - 174

Secondary # Zone/Point Alarm Restore Code

00

175 - 176

Secondary # General Supervisory Restore Code

E2

177 - 178

Secondary # Zone/Point Supervisory Restore Code

00

179 - 180

Secondary # General Fault Restore Code

E3

181 - 182

Secondary # AC Fault Restore Code

E6

183 - 184

Secondary # Zone/Point Fault Restore Code

00

185 - 186

Secondary # Low Battery Fault Restore Code

E8

187 - 188

Secondary # Telco Primary Line Fault Restore Code

EA

189 - 190

Secondary # Telco Secondary Line Fault Restore Code

EB

191 - 192

Secondary # NAC Fault Restore Code

EC

193 - 194

Secondary # Communication Trouble Primary Number Restore Code

ED

195 - 196

Secondary # Communication Trouble Secondary Number Restore Code

EE

197 - 198

Secondary # 485 Communication Trouble Restore Code

EE

199 - 200

Secondary # System Off Normal Restore Code

EF

201 - 202

Secondary # UDACT-F Off Normal Restore Code

EF

203 - 204

Secondary # System 24 Hour Test

99

205 - 206

Secondary # System 24 Hour Test with Active Event

91

207 - 208

Secondary # Manual Test

92

Note: Zero entries prevent the transmission of the report to the Central Station