Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 34

Advertising
background image

Programming Options

34

Document #50049 Rev.E0 1/22/01 P/N 50049:E0

3+1, 4+1 Express and 4+1 Standard Formats

If '0, 2, 4, 6 or 8' is entered for address 16, the following data is automatically programmed for the Primary Phone
number event codes. Enter a '0' for the data setting to disable the report.

TABLE 3-2:

Primary Number Event Codes - 3+1, 4+1 Express and 4+1 Standard

Address

Description

Setting

69

Primary # General Alarm Code

1

70

Primary # Zone/Point Alarm Code

0

71

Primary # General Supervisory Code

8

72

Primary # Zone/Point Supervisory Code

0

73

Primary # General Fault Code

F

74

Primary # AC Fault Code

F

75

Primary # Zone/Point Fault Code

0

76

Primary # Low Battery Fault Code

F

77

Primary # Telco Primary Line Fault Code

F

78

Primary # Telco Secondary Line Fault Code

F

79

Primary # NAC Fault Code

F

80

Primary # Communication Trouble Primary # Code

F

81

Primary # Communication Trouble Secondary # Code

F

82

Primary # 485 Communication Trouble Code

F

83

Primary # System Off Normal Code

F

84

Primary # UDACT-F Off Normal Code

F

85

Primary # General Alarm Restore Code

E

86

Primary # Zone/Point Alarm Restore Code

0

87

Primary # General Supervisory Restore Code

E

88

Primary # Zone/Point Supervisory Restore Code

0

89

Primary # General Fault Restore Code

E

90

Primary # AC Fault Restore Code

E

91

Primary # Zone/Point Fault Restore Code

0

92

Primary # Low Battery Fault Restore Code

E

93

Primary # Telco Primary Line Fault Restore Code

E

94

Primary # Telco Secondary Line Fault Restore Code

E

95

Primary # NAC Fault Restore Code

E

96

Primary # Communication Trouble Primary Number Restore Code

E

97

Primary # Communication Trouble Secondary Number Restore Code

E

98

Primary # 485 Communication Trouble Restore Code

E

99

Primary # System Off Normal Restore Code

E

100

Primary # UDACT-F Off Normal Restore Code

E

101

Primary # System 24 Hour Test

9

102

Primary # System 24 Hour Test with Active Event

F

103

Primary # Manual Test

9

Note: Zero entries prevent the transmission of the report to the Central Station