Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 49

Advertising
background image

Document #50049 Rev. E0 01/22/01 P/N 50049:E0

49

Reporting Formats

The reporting structure for the Ademco Contact ID format is as follows:

For general reports (alarm, trouble and supervisory), the GG and CCC fields are transmitted as 00 and 000 unless
changes to addresses 64 - 65 and 66 - 68 are made.

64 - 65 = Loop number (GG), factory default if 00

66 - 68 = Sensor number (CCC) for General Alarm, Fault or Supervisory messages - factory default is 000.

A typical printout of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:

Notes:

1.

In the sample report, SD46 refers to smoke detector at address 46 or on zone 46. Refer to the charts on the fol-
lowing page as well as “Point Assignments - MS-9200” on page 56 and “Code Wheel Matching Point Assign-
ments - MS-9200” on page 57, for further clarification

2.

18

, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the

alarm and trouble report

3.

Q

, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or

R for New Restore

TABLE A-3:

Ademco Contact ID Reporting Structure

SSSS 18 QXYZ GG CCC

where

SSSS

=

Four digit Subscriber ID (addresses 17 - 20 and 43 - 46)

18

=

Identifies transmission of Contact ID to the receiver at the Central Station

Q

=

Event Qualifier

E = New Event

R = New Restore

XYZ

=

Event code (shown in Table 3-4 on page 36 and Table 3-7 on page 39)

GG

=

Group number or Loop number

CCC

=

Zone or Sensor number

Time

Date

Rcvr/Line ID

SSSS

QXYZ

GG

CCCC

11:28

03/25

11

7777

E110

00

CCCC - general alarm

11:28

03/25

11

7777

E110

00

C046 - alarm SD46

11:28

03/25

11

7777

E300

00

CCCC - general trouble

11:28

03/25

11

7777

E380

00

C046 - trouble SD46

11:28

03/25

11

7777

R110

00

CCCC - general alarm restore

11:28

03/25

11

7777

R110

00

C046 - alarm SD46 restore

11:28

03/25

11

7777

R300

00

CCCC - general trouble restore

11:28

03/25

11

7777

R380

00

C046 - trouble SD46 restore