Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual

Page 33

Advertising
background image

Document #50049 Rev. E0 01/22/01 P/N 50049:E0

33

Programming Options

Programming Event Codes (69-208)

The type of reports and 'event codes' that are sent to the Central Station are referenced in Table 3-2 on page 34, Table
3-3 on page 35, Table 3-4 on page 36, Table 3-5 on page 37, Table 3-6 on page 38 and Table 3-7 on page 39
. The
selections made for the Primary Central Station Number communication Format (address 16) and the Secondary Cen-
tral Station Number Communication Format (address 42) automatically program addresses 69-208 with factory
default selections.

Any of the event codes may be changed. Consult the Central Station prior to altering the event codes. For the 3+1,
4+1 and 4+1 Express formats, entering an event code of '0' will cause the communicator to NOT transmit the report.
Enter '00' for 4+2 and 4+2 Express formats to NOT transmit the report. For Ademco Contact ID format, enter '000'.
Transmission of reports to either or both Central Station phone numbers may be disabled.

Note the special 'System Abnormal Test Report' event code. This report was added per UL DACT requirements. This
report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time the test
report is due to be sent.

Programming the Real-Time Clock

Entering an address greater than 209 will cause a display of the current time. On initial power-up, the clock will start
running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the
first digit to be programmed.

Hours and Minutes

To set the hour, select a digit then press the [ENTER/STORE] key. The digit 2nd from the left will start flashing.
Select a digit then press the [ENTER/STORE] key. The hours setting is completed. With the digit 2nd from the
right flashing, select a digit for the minutes then press the [ENTER/STORE] key. The digit on the far right will start
flashing. Select a digit then press the [ENTER/STORE] key. The minutes setting is completed.

End Programming

Exit Programming Mode by pressing the MODE key, followed by the 4-digit code corresponding to an alternate
mode of operation, then press the [ENTER/STORE] key. During Program Mode, if no key is pressed within 10 min-
utes, the UDACT-F will revert to Normal Mode.

Advertising