KEW3128

25

KEW3128

6. Measurement

   ⑧ 

The measured value will be displayed on the LCD.

   

Release the Button to stop the measurement. Then the measured

results will be displayed on the LCD.

     

Turn the locked Test Button counterclockwise and unlock the Button.

   

This instrument has an auto-discharge function. With the test

leads connected to the circuit under test, release the Test button

to discharge capacitance in the circuit after test.

     

Confirm that the readings on the Voltage monitor becomes 0V.

     

* When the test leads are disconnected from the measured object

during a discharge, keep the same connection and connect the

test leads to the measured object again and continue a discharge.

Attention should be paid when connecting the test leads and the

measured object again so as not to cause aerial discharges between

them for a long period. In this case, a longer discharge period is

required because the internal discharge circuit doesn’t work.

   

⑪  Set the Range Switch toOFFposition, and remove the test

leads from the device under test.

   

Next measurement may not be started when the Test Button is pressed

right after when above step 10 is done. In this case, release the Test

Button and wait for a few seconds, and then press the Test Button.

   

Refer to “

IR Measurement” (=>P.48) and subsequent pages about

the further details of items displayed at each Measurement mode.