KYORITSU 3128 User Manual

Page 3

Advertising
background image

P32 Additional

explanation to “Setting of Measurement Period”

The smallest value of selectable period is 15 seconds.

P41 Additional

explanation to “6.1.6 Filter Mode”

Filter 1 : It uses it to cut the exchange element more than industrial frequency (50/60Hz) when a high electric field

has been generated around the circuit under test.

Filter 2 : Five measured latest data are averaged.

Filter 3 : Filter 1 and Filter 2 are used at the same time.

P.41 Additional explanations to

“6.1.7 Save data”

Logging data (REC file) is recorded and saved in 15 seconds later from the beginning of a measurement.

The data 15 seconds or earlier is shown as

“--“. When viewing a graph on the LCD of the instrument, the

measured results for 15 seconds from the beginning of a measurement are displayed with a straight line.

* It is same in real-time measurements using the supplied software

“KEW Windows”.

The measured value is saved in 15 seconds later from the beginning of a measurement and the data

15 seconds or earlier is shown as

“--“.

Following is an example of the display to be shown on

“KEW Windows”.

P.48 Additional sentences at

“6.3.1 Setting Item”

At IR measurements, continuous measurements over 90 min are possible , however, the displayable area of

the recorded data, graph and analyzed data are 90 min of measured results. The later portions are displayed

with numbers only.