MULTI-PARAMETER TRANSMITTER USER’S MANUAL

Section 3 - Electrical Connections and Setup

Section 3 - Electrical Connections and Setup

Page 7

3.3 pH and ORP Differential Probe connections and setup

The drawing shows the connections for the Aquametrix Differential (5 wire) probe. The cable
should be run in a conduit separate from AC power wires, and via a separate conduit hole.

Figure 3.2 Connections for Differential (5 wire) pH or ORP probe

SELECT pH SEC. 4.6

MANUAL CALIBRATE

SELECT DIFFERENTIAL PROBE

pH PROBE SEC. 4.1
or ORP PROBE SEC. 5.1

pH SEC. 4.7 or ORP SEC. 5.6
(IF NECESSARY)

or ORP SEC. 5.5
(IF NECESSARY)

MANUAL CAL PH

7.15pH 25.0C

PROBE SELECT

METER SELECTION

RUN MODE

Once connected, step through the LCD menus to
select the probe in the order shown. The first two
steps may be skipped if the meter is already con-
figured for pH or ORP and a Differential Probe.
When using a pH probe, it is important to ensure
that the transmitter is reading the probe tempera-
ture correctly for accurate temperature compensa-
tion. The ORP probe does not require temperature
compensation, although the transmitter can dis-
play process temperature measured by the probe.
The factory temperature calibration is usually
accurate enough that no adjustments are neces-
sary.

Dwg# N104-42