Output 1, General, Relay – West Control Solutions N6600 User Manual

Page 103: Ssr drive/ttl, Solid state

Advertising
background image

A.4

OUTPUT 1

General

Types Available:

Relay, SSR Drive/TTL and Solid State.

Relay

Contact Type:

Single pole double throw (SPDT).

Rating:

2A resistive at 120/240V AC.

Lifetime:

>500,000 operations at rated

voltage/current.

Isolation:

Inherent.

SSR Drive/TTL

Drive Capability:

SSR >10V DC into 500

minimum.

Isolation:

Not isolated from input or other SSR outputs.

Solid State

Operating Voltage Range:

20 - 280Vrms (47 - 63Hz)

Current Rating:

0.01 - 1A (full cycle rms on-state @ 25

°

C);

derates linearly above 40

°

C to 0.5A @

80

°

C.

Max. Non-repetitive Surge

Current (16.6ms):

25A peak

Min. OFF-State

dv

dt

@ Rated

Voltage:

500V/

µ

s

Max. OFF-State leakage @

Rated Voltage:

1mA rms

Max. ON-State Voltage

Drop @ Rated Current:

1.5V peak.

Repetitive Peak OFF-state

Voltage, Vdrm:

600V minimum.

S075-A

A-4

PM-0075

Advertising