L {N} {P} {DATA} N *

where {DATA} is indeterminate. If the immediately-preceding message received

by the slave Controller was not a Type 3 message, the Type 4 message is ignored.

O075-5

5-5

PM-0075

{DATA} Content

Sign/Decimal Point Position

{DATA} Content

Sign/Decimal Point Position

abcd0

+abcd

abcd5

abcd

abcd1

+abc.d

abcd6

abc.d

abcd2

+ab.cd

abcd7

ab.cd

Table 5-1 {DATA} Element - Sign and decimal Point Position

Identifier

Parameter/Command

Identifier

Parameter/Command

A

Setpoint High Limit

W

Output Power (Read Only if not in

Manual Control)

B

Output 1 Power Limit

Z

Controller Commands

3

C

Alarm 1 value

[

Recorder Output Scale Max.

D

Rate (Derivative Time Constant)

1

\

Recorder Output Scale Min.

E

Alarm 2 value

]

Scan Table

F

ON/OFF Differential

^

Setpoint Ramp Rate

G

Scale Range Max. (Read Only)

a

Alarm 1 Hysteresis value

H

Scale Range Min. (Read Only)

b

Alarm 2 Hysteresis value

I

Reset (Integral Time Constant)

1

c

Heater Current High Scale Limit

J

Manual Reset (Bias)

d

Heater Current Nominal Value

K

Overlap/Deadband

e

Heater Current (Read Only)

L

Controller Status

2

f

High Heater Break Alarm value

M

Process Variable

g

Low Heater Break Alarm value

N

Output 1 Cycle Time

h

AM Key Usage (Read Only)

O

Output 2 Cycle Time

i

Control Setpoint value (Read Only)

P

Proportional Band 1

1

j

Soft Start Setpoint value

Q

Scale Range Decimal Point Position

(Read Only)

k

Soft Start Time value

S

Setpoint value

l

Soft Start Time Remaining (Read

Only)

T

Setpoint Low Limit

m

Input Filter Time Constant

U

Proportional Band 2

1

v

Process Variable Offset value

V

Deviation value

Table 5-2 Commands/Parameters and Identifiers