Set up mode parameters, Table 3-1 set up parameters, 2 set up mode parameters – West Control Solutions N6600 User Manual

Page 18

Advertising
background image

3.2

SET UP MODE PARAMETERS

3-2

O075-3

PM-0075

Parameter

Legend

Adjustment Range

Default

Input Filter Time

Constant

OFF, 0.5s to 100.0s In 0.5s

increments

2.0s

Process Variable Offset

±

input span of Controller

0

Output Power

0 to 100%

Read Only

Output Power 2

4

0 to 100%

Read Only

Proportional Band 1

0.0% to 999.9% of input span

10.0%

Proportional Band 2

14

,

0.0% to 999.9% of input span

10.0%

Reset (Integral Time

Constant)

1

1s to 99m 59s and OFF.

5m 00s

Rate (Derivative Time

Constant)

1

00s to 99m 59s

1m 15s

Overlap/Deadband

1 4

,

20% to + 20% of Proportional

Band 1 + Proportional Band 2

0%

Manual Reset (Bias)

1

0% to 100% (single output)

100% to +100% (dual output)

25%

ON/OFF Differential

2

:

Output 1 only

Output 2 only

4

Outputs 1 & 2

4

0.1% to 10% of input span

0.5%

Setpoint High Limit

Setpoint to Range Max.

Range

Max.

Setpoint Low Limit

Range Min. To Setpoint

Range

Min.

Table 3-1 Set Up Parameters