4

MODBUS RTU COMMUNICATIONS

The Plastics Controller may be equipped with two-wire RS485-compatible serial

communications, by which means communication may occur between the

Controller and a master device (e.g. a computer or terminal).

4.1

COMMUNICATIONS WRITE ENABLE/DISABLE

When Communications Write operations are enabled (in Set Up Mode - see

Subsection 3.2.39), the Controller parameters may be adjusted by the master

device via the serial communications link. If communications Writes are disabled,

the Controller will not adjust or change any parameters in response to commands

received from the master device and will send a negative acknowledgement in

response to such commands. Whether communications Writes are enabled or

disabled, the Controller will return the requested information in response to

interrogation from the master device.

4.2

PHYSICAL REQUIREMENTS

4.2.1 Character Transmission

The data format is fixed to be one start bit, eight data bits and one stop bit. The

Baud rate may be selected to be 1200, 2400, 4800 (default) or 9600 Baud. The

parity is selectable to be even, odd, or none.

4.2.2 Line Turn-round

The line turn-round timings adhere to the industry standard.

4.3

MODBUS RTU PROTOCOL

The standard RS485 Communications Option and the Enhanced RS485

Communications option both use the industry standard MODBUS protocol. The

following restrictions are imposed:

Baud rates may be set to 1200, 2400, 4800 or 9600 Baud only.

Support for multi-parameter Write operations is limited to support of the

Multi-Word Write Function (Number 16) but permits writing of one

parameter only per message.

The multi-parameter Read operations support a maximum of 10

parameters per message.

The following MODBUS functions are supported (JBUS names, where applicable,

are given in italics):

O075-4