Loop control – West Control Solutions N6600 User Manual

Page 106

Advertising
background image

DC

Resolution:

Eight bits in 250mS (10 bits in 1 second

typical, >10 bits in >1 second typical).

Accuracy:

±

0.25% (mA at 250

, V at 2 k

). Degrades

linearly to

±

0.5% for increasing load

burden (to limit as stated below).

Update Rate:

Every control algorithm execution.

Ranges:

0 - 20mA

4 - 20mA

0 - 5V

0 - 10V

(Changes between V and mA require link jumper movement.)

Load Impedance:

0 - 20mA: 500

maximum

4 - 20mA: 500

maximum

0 - 5V: 500

minimum

0 - 10V: 500

minimum

Isolation:

Isolated from all other inputs and outputs.

Range Selection Method:

Link jumper.

A.7

LOOP CONTROL

Automatic Tuning Types:

Pre-Tune and Self-Tune.

Proportional Bands:

0 (OFF), 0.5% - 999.9% of input span at

0.1% increments.

Reset (Integral Time

Constant):

1s - 99min 59s and OFF

Rate (Derivative Time

Constant):

0 (OFF) - 99 min 59 s.

Manual Reset (Bias):

Added each control algorithm execution.

Adjustable in the range 0 - 100% of output

power (single output) or –100% to +100%

of output power (dual output).

Deadband/Overlap:

–20% to +20% of Proportional Band 1 +

Proportional Band 2.

ON/OFF Differential:

0.1% to 10.0% of input span.

A-7

S075-A

PM-0075