primary winding of which carries the heater current. The current carried by the

primary winding and the transformer ratio are then taken into account when

setting the Heater Current parameters (see Volume 1, Section 3).

1.3.8 Relay Outputs

The contacts are rated at 2A resistive at 120/240V AC.

1.3.9 SSR Drive Outputs

These outputs produce a time-proportioned non-isolated DC signal:

Output 1:

>10V DC into 500

minimum

Output 2:

>4.5V DC into 250

minimum

1.3.10 Solid State Outputs

These outputs provide up to 1A AC drive with a longer lifetime than an

electromechanical relay. For further details, refer to Appendix A.

1.3.11 DC Outputs

Only Output 3 may be a DC output (Recorder Output only). See Appendix A.

1.3.12 RS485 Serial Communications Link

The cable used should be suitable for data transfer at the selected rate (1200,

2400, 4800 or 9600 Baud) over the required distance. Transmitters/receivers

conform to the recommendations in the EIA Standard RS485.

The “A" terminal on the Controller should be connected to the “A” terminal on the

master device; the “B" terminal on the Controller should be connected to the “B”

terminal on the master device. Where several Controllers are connected to one

master port, the master port transceiver in the active state should be capable of

driving a load of 12k

per Controller; the master port transceiver in the passive

state must have pull-up/pull-down resistors of sufficiently low impedance to ensure
that it remains in the quiescent state whilst supplying up to

±

100

µ

A each to the

Controller transceivers in the high impedance state.

NOTES:

1. The RS485 Serial Communications option and the Dual Setpoint/Quick

Transfer option are mutually exclusive.

2. The Controller receiver presents

1

4

standard RS485 unit load. The total

receiver load on the communications system must not exceed 32 standard

RS485 unit loads.

S075-1

1-7

PM-0075