3.2.1 Input Filter Time Constant

The Controller input is equipped with a digital filter which is used to filter out any

extraneous impulses on the process variable. This filtered PV is used for all

PV-dependent functions (control, alarms etc.). The time constant for this filter may

be adjusted in the range 0.0 seconds (filter OFF) to 100.0 seconds in 0.5 second

increments. The default setting is 2.0 seconds.

CAUTION: If this parameter is set to an excessively high value, the control

quality may be significantly impaired. The value chosen should be

sufficiently large to attenuate stray noise on the process variable signal but

no larger.

3.2.2 Process Variable Offset

This parameter is used to modify the actual process variable value (measured at

the Controller’s input terminals) in the following manner:

Offset PV value = Actual PV value + Process Variable Offset value.

O075-3

3-5

PM-0075

NOTES ON TABLE 3-1

1. These parameters are not operative if the Proportional Band = 0.

2. Switching differential with ON/OFF Control Output.

3. These parameters are optional; only one legend will appear for each alarm.

4. Only applicable if Output 2 is fitted.

5. Appears only if ramp rate

rp

is not switched OFF.

6. Applicable only if the Communications Option PCB is fitted.

7. Does not appear in Operator Mode unless

rPEN

= 1.

8. For Single Setpoint operation, the legend displayed is

SP

; for Dual Setpoint

operation, the legend displayed is

SP1

.

9. Applicable only when Heater Break Alarm Strategy is configured to Percentage

Mode.

10. Does not appear if Heater Break Input Type is configured to be SCRi.