3.2.8 Rate (Derivative Time Constant)

This parameter is adjustable in the range 00 seconds to 99 minutes 59 seconds.

This parameter is not applicable if Proportional Band 1 (see Subsection 3.2.5) is set

to 0 (ON/OFF control).

3.2.9 Overlap/Deadband

This defines the portion of the Proportional Band (Proportional Band 1 +

Proportional Band 2) over which both outputs are active (or, in the case of a

deadband, neither output is active). It is adjustable within the range –20% to

+20% (negative value = deadband). The default value is 0%. The function of the

overlap/deadband is illustrated in Figure 3-1. This parameter is not applicable if

Proportional Band 1 = 0 or if Output 2 is not fitted.

Note that, with Output 2 set to ON/OFF control (Figure 3-1 Case 3), the

Overlap/Deadband parameter has the effect of moving the ON Differential band

of Output 2 to create an overlap (positive values) or a deadband (negative

values). When Overlap/Deadband = 0, the “Output 2 OFF” edge of the Output 2

ON/OFF Differential band coincides with the point at which Output 1 reaches 0%.

3.2.10 Bias (Manual Reset)

This bias to the output power is expressed as a percentage of output power and is

adjustable in the range 0% to 100% (if only Output 1 is fitted) or –100% to +100%

(if both outputs are fitted). Its default value is 25%. This parameter is not

applicable if Proportional Band 1 = 0.

3.2.11 ON/OFF Differential (Hysteresis)

This is a switching differential used when one or both outputs have been set to

ON/OFF control (i.e. Proportional Band 1 or Proportional Band 2 or both = 0). This

parameter may be adjusted within the range 0.1% to 10.0% of the input span of

the Controller. The default value is 0.5%.

3.2.12 Setpoint High Limit

This is the maximum limit for setpoint adjustment. It should be set to a value which

prevents the setpoint being given a value which will cause damage to the

process being controlled. The Setpoint High Limit may be adjusted between the

current setpoint value and Input Range Maximum. The default value is Input

Range Maximum.

3.2.13 Setpoint Low Limit

This is the minimum limit for setpoint adjustment. It should be set to a value which

prevents the setpoint being given a value which will cause damage to the

3-8

O075-3

PM-0075