West Control Solutions N6600 User Manual

Page 43

Advertising
background image

O075-4

4-7

PM-0075

Parameter

No.

Notes

Comms. Write Status

1

Read Only. 1 = enabled, 0 = disabled

Auto/Manual Control

2

1 = Manual, 0 = Auto

Self-Tune

4

3

1 = activate(d), 0 = dis-engage(d)

Pre-Tune

5

4

1 = activate(d), 0 = dis-engage(d)

Alarm 1 Status

5

Read Only. 1 = active, 0 = inactive

Alarm 2 Status

6

Read Only. 1 = active, 0 = inactive

Setpoint Ramp Enable/Disable

7

1 = enable(d), 0 = disable(d)

Parameter Changed

2

8

Read Only. 1 = change, 0 = no change

Auto/Output Turn-Off

3

9

1 = Output Turn-Off, 0 = Auto Control

High Heater Break Alarm Status 10 Read Only. 1 = active, 0 = inactive
Low Heater Break Alarm Status

11 Read Only. 1 = active, 0 = inactive

Short-Circuit Heater Break

Alarm Status

12 Read Only. 1 = active, 0 = inactive

Heater Break Current Transfer

(Quick Transfer)

13 1 = initiate transfer, 0 = no transfer.

This bit will always be 0 when read.

Short-Circuit Heater Break

Alarm Enable/Disable

14 1 = enable(d), 0 = disable(d)

Reserved

15

Reserved

16

NOTES

1. Not available if AM Key Usage (see Subsection 3.2.37) is not set to Auto/Manual

Control Selection.
2. This indicates whether a parameter has been changed from the front panel

since the last interrogation via the communications link. Every interrogation of this

bit resets it to 0.

3. Not available if AM Key Usage (see Subsection 3.2.37) is not set to Auto/Output

Turn-Off Selection.
4. If Setpoint Ramping is enabled, an Activate Self-Tune command will not take

effect until the setpoint has reached its target value.
5. An Activate Pre-Tune command will fail if the process variable is within 5% of

input span from the setpoint.
6. Not available if Heater Break Input Type is configured to be SCRi.
7. Available only if Heater Break Alarm Strategy is set to Percentage Mode.

Table 4-1 MODBUS Bit Parameters