5.3.2.3 OUTPUT 1 CYCLE TIME {P} = N

This parameter may be modified/interrogated using a Type 2 message or a Type

3/4 message sequence. The value to which this is set is dependent upon the

output type and the nature of the process to be controlled. For relay outputs, this

parameter should be set to as large a value as possible (consistent with

satisfactory control of the process) in order that the life of the relay be maximised.

For SSR Drive and Solid State outputs, lower values may be used. The decimal

point position is set to 0 for all except the 0.5s value (00051).

NOTE: Cycle Time values must be written correctly if a Type 3/4 message

sequence is used i.e. the value must be a power of 2 in the range 0.5 - 512

(0.5, 1, 2, 4, 8, etc.).

5.3.2.4 OUTPUT 2 CYCLE TIME {P} = O

This parameter may be modified/interrogated using a Type 2 message or a Type

3/4 message sequence. The value to which this is set is dependent upon the

output type and the nature of the process to be controlled. For relay outputs, this

parameter should be set to as large a value as possible (consistent with

satisfactory control of the process) in order that the life of the relay be maximised.

For SSR Drive and Solid State outputs, lower values may be used. The decimal

point position is set to 0 for all except the 0.5s value (00051).

NOTE: Cycle Time values must be written correctly if a Type 3/4 message

sequence is used i.e. the value must be a power of 2 in the range 0.5 - 512

(0.5, 1, 2, 4, 8, etc.).

5.3.2.5 RECORDER OUTPUT SCALE MAXIMUM VALUE {P} = [

This parameter may be modified/interrogated using a Type 2 message or a Type

3/4 message sequence. It defines the maximum scale value for the Controller’s

Recorder Output and may be adjusted within the range –1999 to 9999. This value

corresponds to the Input Scale Maximum and the decimal point position will

always be the same as that for the input.

NOTE: If this parameter is set to a value less than the Recorder Output

Minimum Value, the Recorder Output sense is reversed.

5.3.2.6 RECORDER OUTPUT SCALE •MINIMUM VALUE {P} = \

This parameter may be modified/interrogated using a Type 2 message or a Type

3/4 message sequence. It defines the minimum scale value for the Controller’s

Recorder Output and may be adjusted within the range –1999 to 9999. This value

corresponds to the Input Scale Minimum and the decimal point position will

always be the same as that for the input.

NOTE: If this parameter is set to a value greater than the Recorder Output

Maximum Value, the Recorder Output sense is reversed.