Output 3, General, Relay – West Control Solutions N6600 User Manual

Page 105: Solid state

Advertising
background image

Max. OFF-State leakage @

Rated Voltage:

1mA rms

Max. ON-State Voltage

Drop @ Rated Current:

1.5V peak.

Repetitive Peak OFF-state

Voltage, Vdrm:

600V minimum.

A.6

OUTPUT 3

General

Types Available:

Relay or Solid State (Alarm only) or DC

linear (Recorder Output only)

Relay

Contact Type:

Single pole double throw (SPDT).

Rating:

2A resistive at 120/240V AC.

Lifetime:

>500,000 operations at rated

voltage/current.

Isolation:

Inherent.

Solid State

Operating Voltage Range:

20 - 280Vrms (47 - 63Hz)

Current Rating:

0.01 - 1A (full cycle rms on-state @ 25

°

C);

derates linearly above 40

°

C to 0.5A @

80

°

C.

Max. Non-repetitive Surge

Current (16.6ms):

25A peak

Min. OFF-State

dv

dt

@ Rated

Voltage:

500V/

µ

s

Max. OFF-State leakage @

Rated Voltage:

1mA rms

Max. ON-State Voltage

Drop @ Rated Current:

1.5V peak.

Repetitive Peak OFF-state

Voltage, Vdrm:

600V minimum.

S075-A

A-6

PM-0075

Advertising