ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 103

Alarm parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Alarm 1 Type

0

Process High Alarm

1

Process Low Alarm

2

Deviation Alarm (SP-PV)

3

Band Alarm

4

Loop Alarm

5

Input/Sensor Break Alarm

6

Auxiliary Input A Break Alarm

Alarm 1 Type

6144

0x1800

R/W

7

Auxiliary Input B Break Alarm

Alarm 1 Value

6145

0x1801

R/W

Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.

Alarm 1 Hysteresis

6146

0x1802

R/W

Limited by the input span
Value

Alarm 1 Inhibit Enable

0

Disabled

Alarm 1 Inhibit
Enable/disable

6147

0x1803

R/W

1

Enabled

Value

Alarm 1 Status

0

Inactive

Alarm 1 Status

6148

0x1804

RO

1

Active

Value

Alarm 1 Inhibit Status

0

Not Inhibited

Alarm 1 Inhibit
Status

6149

0x1805

RO

1

Inhibited

Value

Alarm 2 Type

0

Process High Alarm

1

Process Low Alarm

2

Deviation Alarm (SP-PV)

3

Band Alarm

4

Loop Alarm

5

Input/Sensor Break Alarm

6

Auxiliary Input A Break Alarm

Alarm 2 Type

6160

0x1810

R/W

7

Auxiliary Input B Break Alarm

Alarm 2 Value

6161

0x1811

R/W

Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.

Alarm 2 Hysteresis

6162

0x1812

R/W

Limited by the input span
Value

Alarm 2 Inhibit Enable

0

Disabled

Alarm 2 Inhibit
Enable/disable

6163

0x1813

R/W

1

Enabled

Value

Alarm 2 Status

0

Inactive

Alarm 2 Status

6164

0x1814

RO

1

Active

Value

Alarm 2 Inhibit Status

0

Not Inhibited

Alarm 2 Inhibit
Status

6165

0x1815

RO

1

Inhibited