Conditions for use, Operating conditions, Standards – West Control Solutions ProVU 4 User Manual

Page 181: Dimensions

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 180

Specifications

59407, Issue 1 – March 2008

Conditions For Use

Reference Test Conditions

Ambient Temperature:

20C ±2C.

Relative Humidity:

60 to 70%.

Supply Voltage:

100 to 240V AC 50Hz ±1%.

Source Resistance:

<10Ω for thermocouple input.

RTD Lead Resistance:

<0.1Ω/lead balanced (Pt100).

Operating Conditions

Ambient Temperatures

0C to 55C (operating) and -20C to 80C (storage).

Relative Humidity:

20% to 95% non-condensing.

Altitude:

Up to 2000m above sea level.

Supply Voltage:

Either 100 to 240V ±10% AC 50/60Hz
or 20 to 48V AC 50/60Hz & 22 to 55V DC for low voltage versions.

Power Consumption:

Mains versions: 20VA.
Low voltage versions: 15VA / 12W.

Source Resistance:

1000Ω maximum (thermocouple).

RTD Input Lead
Resistance:

50Ω per lead maximum, balanced

Standards

Conformance Norms:

CE, UL, ULC.

EMC standards:

Complies with CE EN61326.

Safety Standards:

Complies with CE EN61010-1 and UL3121.
Pollution Degree 2, Installation Category II.

Front Panel Sealing:

To IP66 (IP65 front USB connector). IP20 behind the panel.
(Not recognised / approved by UL)

Dimensions

Front Bezel Size:

1

/

4

DIN (96 x 96mm).

Mounting:

Plug-in with panel mounting fixing strap.

Panel Cut-out Size:

92mm x 92mm (

1

/

4

DIN instruments).

Depth Behind Panel:

117mm (

1

/

16

DIN instruments).

Ventilation

20mm gap required above, below and behind.

Weight:

0.65kg maximum.

Terminals:

Screw type (combination head).

Advertising