West Control Solutions ProVU 4 User Manual

Page 29

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 28

Wiring Instructions

59407, Issue 1 – March 2008

Universal Input Connections – PT100 / NI120 (RTD) input

For three wire RTDs, connect the resistive leg and the common legs of the RTD as
illustrated. For a two wire RTD a wire link should be used in place of the third wire (shown by
dotted line). Two wire RTDs should only be used when the leads are less than 3 metres long.
Avoid cable joints.

Figure 12.

RTD Input Connections

Four wire RTDs can be used, provided that the fourth wire is left unconnected. This wire
should be cut short or tied back so that it cannot contact any of the terminals on the rear of
the instrument.

Universal Input Connections - Linear Volt, mV or mA input

Linear DC voltage, millivolt or milliamp input connections are made as illustrated. Carefully
observe the polarity of the connections.

Figure 13.

DC Volt, mV & mA Input Connections

RTD

3

2

1

4

3

2

1

+

_

_

+

mA

mV/V

Advertising