Creating, editing or inserting segments – West Control Solutions ProVU 4 User Manual

Page 117

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 116

Modbus Parameters

59407, Issue 1 – March 2008

Creating Or Editing A Profile Header - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Profile Start Signal Low Byte

A/R

A/R

Time/day

Profile Start Time (Byte 4 - High)
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Profile Start Time (Byte 1 - Low)

Floating point number

Profile Start Day High Byte

00

00

Profile Start Day Low Byte

A/R

A/R

1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday, 10 = Saturday
And Sunday, 11= All Week

Profile Starting Setpoint High

00

00

Profile Starting Setpoint Low

A/R

A/R

0 = Current Setpoint, 1 = Current Process
Variable Value

Profile Recovery High Byte

00

00

Profile Recovery Low Byte

A/R

A/R

0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint
3 = Use controller setpoint, 4 = Continue
profile from where it was when power failed

Profile Recovery Time (Byte 4 - high)
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Profile Recovery Time (Byte 1 - Low)

Floating point number

Profile Abort action High Byte

00

00

Profile Abort Action Low Byte

A/R

A/R

0 = Control to off
1 = Maintain last profile setpoint
2 = Use controller setpoint

Profile Cycles High Byte

A/R

A/R

Profile Cycles Low Byte

A/R

A/R

1 to 9999 or 10,000 for “Infinite”

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

The instrument replies to this message with an Edit Response Message.

Creating, Editing or Inserting Segments

Creating new segments is only possible when a new profile is being created (see above for
instruction for creating a profile at the next available position, or at a position that you
specify). An error is returned if the correct sequence is not followed.
The Insert Segment command is used to add segments to an existing profile (one that
already has an end segment). This inserts a new segment at the position specified.
The Edit Segment command is used to alter segments of an existing profile.
The segment number is in relation to the profile number, e.g. to edit or insert a segment at
position 3 of profile 1 the segment number will be 3, and to edit or insert a segment at
position 3 of profile 6 the segment number will also be 3.

Creating, Editing or Inserting Segments - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument.

Function Code

23

17

Requires the multi read/write function.

Read Start Address High Byte

32

20

Read Start Address Low Byte

06

06

Advertising