Option slot 1 parameters – West Control Solutions ProVU 4 User Manual

Page 88

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 87

Option Slot 1 Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Module Fitted In Slot 1

0

None Fitted

1

Single Relay

2

Single SSR Driver

3

Linear mA/V DC

8

Triac

Option Slot 1
Module Type

2130

0x0852

RO

255

Error (unrecognised module)

Value

Linear Output 1 Type

0

0 to 5V DC

1

0 to 10V DC

2

2 to 10V DC

3

0 to 20mA DC

4

4 to 20mA DC

Linear mA/V DC
Output 1 Type

2131

0x0853

R/W

5

Variable 0 to 10VDC Transmitter PSU

Value

Digital Output 1 Status

0

Inactive

Digital Output 1
Status

2132

0x0854

RO

1

Active

Linear Output 1
Level Status

2134

0x0856

RO

-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value

Linear Output 1 Function

0

Disabled

1

Primary Output Power

2

Secondary Output Power

3

Retransmit Actual Setpoint Value

Linear Output 1
Function

2144

0x0860

R/W

4

Retransmit Process Variable Value

Value

Digital Output 1 Function

0

Disabled

1

Primary Output Power

2

Secondary Output Power

3

Alarm

Digital Output 1
Function

2146

0x0862

R/W

4

Alarm and Event

Value

Output 1 Alarm Selection

0

Alarm 1. Direct Acting

1

Alarm 1. Reverse Acting

2

Alarm 2, Direct Acting

3

Alarm 2. Reverse Acting

4

Alarm 3. Direct Acting

5

Alarm 3. Reverse Acting

6

Alarm 4. Direct Acting

7

Alarm 4. Reverse Acting

8

Alarm 5. Direct Acting

9

Alarm 5. Reverse Acting

10

OR of Alarm 1 or 2. Direct

Output 1 Alarm
Selection

2148

0x0864

R/W

11

OR of Alarm 1 or 2. Reverse