The Auto-Hold Feature

Each profile segment has individual Auto-Hold settings. If utilised, these ensure that the
profile and the actual process remain synchronised. If the process does not closely match
the required setpoint by remaining within the Hold Band, the profile can be held until it
returns within bounds.
The user can choose to hold the profile if the process beyond the Hold Band Above The
Setpoint
only, Below The Setpoint only or to Band (either side of the setpoint). When Auto-
Hold is active, the profile status is shown as “Held”.

Held if Auto-Hold set to Above Setpoint or Band

Dwell Segment

Setpoint

Hold Band

Process Variable

Held if Auto-Hold set to Below Setpoint or Band

Figure 41.

Auto-Hold On A Dwell Segment

During a Dwell, the dwell time is increase by the time that the process is outside of the hold
band in the selected direction(s).

Held if Auto-Hold set to Above Setpoint or Band

Process Variable

Ramp Setpoint

(without Auto-

Hold)

Hold Band

Ramp Setpoint
(with Auto-Hold)

Held if Auto-Hold set to Below Setpoint or Band

Figure 42.

Auto-Hold On A Ramp Segment

During a Ramp segment, the ramp is held at the current setpoint value while the process is
outside of the hold band in the selected direction(s). The time taken to complete the ramp is
increased by the time taken by the Auto-Hold.