ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 120

Modbus Parameters

59407, Issue 1 – March 2008

Get Segments Remaining

Returns the number of unused segments remaining in the instrument. The number will be
between 0 and 255, depending on how many have been used in the profiles so far created.

Get Segments Remaining - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument as
required

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

06

06

Read Quantity Of Registers High

00

00

Read Quantity Of Registers Low

01

01

Write Start Address High

32

20

Write Start Address Low

06

06

Write Quantity Of Registers High

00

00

Write Quantity Of Registers Low

01

01

Byte Count

02

02

Command Code High Byte

83

53

Command Code Low Byte

82

52

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

The instrument replies to this message with an Edit Response Message.

Edit Response Message From Instrument

The instrument replies to each the profile or segment creation, edit or delete message with a
Edit Response Message. The same format is used when replying to the Get Segments
Remaining request.

Edit Response Message - Response (from instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

The multi read/write function

Byte Count

02

02

Command Response High Byte

A/R

A/R

Command Response Low Byte

A/R

A/R

Two data bytes containing the
Command Response data (see below)

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R