Page 81

Function 23 Hex - Read / Write Multiple Registers (0x17 hex)

Reads and writes the requested number of consecutive words (two-bytes) starting at the
specified addresses.

QUERY

Values to Write

Function

1

st

Read

Address

Number of

Words to

Read

1

st

Write

Address

Number of

Words to

Write

1

st

Word

2

nd

Word

etc

Last Word

17

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

RESPONSE

Read Data

Function

Number of

Bytes

1

st

Word

2

nd

Word

etc

Last Word

17

HI

LO

HI

LO

HI

LO

HI

LO

Note:

The number of data that can be read and written in one message is 253 bytes.

Exception Responses

When a QUERY is sent that the instrument cannot interpret then an Exception RESPONSE
is returned. Possible exception responses are:

Exception Code

Error Condition

Interpretation

00

Unused

None.

01

Illegal function

Function number out of range.

02

Illegal Data Address

Write functions: Parameter number out of range or not
supported. (for write functions only).
Read Functions: Start parameter does not exist or end
parameter greater than 65536.

03

Illegal Data Value

Attempt to write invalid data / required action not executed.

The format of an exception response is:

RESPONSE

Function

Exception Code

Original Function code with its Most
Significant Bit (MSB) set.

as detailed above

Note:

In the case of multiple exception codes for a single QUERY the Exception code returned is
the one corresponding to the first parameter in error.