ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 124

Modbus Parameters

59407, Issue 1 – March 2008

Read A Segment - Response (from instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

The multi read/write function

Byte Count

02

18

Command Response High Byte

82

52

Command Response Low Byte

83

53

Profile Number High Byte

A/R

A/R

Profile Number Low Byte

A/R

A/R

Segment Number High Byte

A/R

A/R

Segment Number Low Byte

A/R

A/R

Segment Type High Byte

00

00

Segment Type Low Byte

A/R

A/R

0 = Ramp Time, 1 = Ramp Rate,
2 = Step, 3 = Dwell, 4 = Hold, 5 = Loop
6 = Join, 7 = End, 8 = Repeat sequence
then end

Segment Info A (Byte 4 - High)
Segment Info A (Byte 3)
Segment Info A (Byte 2)
Segment Info A (Byte 1 - Low)

Floating point number

The meaning of the data contained in
Segment Info A depends on the type of
segment it relates to. See below.

Segment Info B (Byte 4 - High)
Segment Info B (Byte 3)
Segment Info B (Byte 2)
Segment Info B (Byte 1 - Low)

Floating point number

The meaning of the data contained in
Segment Info B depends on the type of
segment it relates to. See below.

Auto Hold Type High Byte

A/R

A/R

Auto Hold Type Low Byte

A/R

A/R

0 = Auto-Hold Off, 1 = Hold above SP,
2 = Hold below SP,3 - Hold above and
below SP

Auto Hold Value (Byte 4 - High)
Auto Hold Value (Byte 3)
Auto Hold Value (Byte 2)
Auto Hold Value (Byte 1 - Low)

Floating point number

Events High Byte

00

00

Events Low Byte

A/R

A/R

The status of the five events are defined by
the lowest 5 bits of the low byte. A bit value
of 1 signifies the event is on.
Bit 0 = event 1, bit 1 = event 2, bit 3 =
event 4 and bit 5 = event 4.

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R