Universal process input parameters – West Control Solutions ProVU 4 User Manual

Page 84

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 83

Universal Process Input Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Process Input Type

0

B Type Thermocouple

2

C Type Thermocouple

4

D Type Thermocouple

6

E Type Thermocouple

8

J Type Thermocouple

10

K Type Thermocouple

12

L Type Thermocouple

14

N Type Thermocouple

16

R Type Thermocouple

18

S Type Thermocouple

20

T Type Thermocouple

22

PtRh 20%: 40% Thermocouple

24

PT100 RTD

26

NI120 RTD

28

0 to 20mA DC

29

4 to 20mA DC

30

0 to 50mV DC

31

10 to 50mV DC

32

0 to 5V DC

33

1 to 5V DC

34

0 to 10V DC

Universal Process
Input Type

1024

0x0400

R/W

35

2 to 10V DC

Value

Engineering Units

0

= None

1

= °C (Default for Europe)

Engineering Units

1025

0x0401

R/W

2

= °F (Default for USA)

Value

Decimal Places

0

None (e.g. 1234)

1

One (e.g. 123.4)

2

Two (e.g. 12.34)

Maximum Display
Decimal Places

1026

0x0402

R/W

3

Three (e.g. 1.234)

Range Minimum

1027

0x0403

R/W

Range Maximum

1028

0x0404

R/W

Valid between input range maximum and minimum
(see Specifications Section for input details)

Process Variable
Offset

1029

0x0405

R/W

Valid between scale range maximum and minimum

Filter Time Constant

1030

0x0406

R/W

Valid between 0.0 and 512.0

Process Variable

1031

0x0407

RO

The current process input value
Value

Process Input Break Status

0

Inactive

Input Signal /Sensor
Break Flag

1032

0x0408

RO

1

Active