Option slot a parameters – West Control Solutions ProVU 4 User Manual

Page 86

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 85

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Scale Point 14

1080

0x0438

R/W

>Scale point 13 to 100.0%

Display Point 14

1081

0x0439

R/W

Valid between scale range maximum and minimum

Scale Point 15

1082

0x043A

R/W

>Scale point 14 to 100.0%

Display Point 15

1083

0x043B

R/W

Valid between scale range maximum and minimum

Option Slot A Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Digital Input A Status

0

Inactive

Digital Input A Status

2115

0x0845

RO

1

Active

Value

Module Fitted In Slot A

0

None Fitted

1

RS485 Communications

3

Digital Input

4

Auxiliary Input A

5

Ethernet Communications

Option Slot A
Module Type

2116

0x0844

RO

255

Error (unrecognised module)

Value

RS485 Address

0

Modbus Master mode

RS485 Address

2117

0x0845

R/W

1 to 255

Modbus Slave Address

Value

Baud Rate

0

4800

1

9600

2

19200 (Default)

3

38400

4

57600

RS485 Data Rate

2118

0x0846

R/W

5

115200

Value

Parity

0

None

1

Even

RS485 Parity

2119

0x0847

R/W

2

Odd

Value

Auxiliary A Input Type

0

0 to 20mA DC

1

4 to 20mA DC

2

0 to 10V DC

3

2 to 10V DC

4

0 to 5V DC

Auxiliary Input A
Type

2120

0x0848

R/W

5

1 to 5V DC

Target Setpoint
Address

2121

0x0849

R/W

Target setpoint parameter address for master mode

Value

Data Format

0

Integer

1

Integer with 1 decimal place

Master Transmit
Format

2123

0x084B

R/W

2

Floating point number