17 Appendix 2 - Specifications

Universal Process Input

General Input Specifications

Input Sample Rate:

Ten samples per second.

Digital Input Filter
time constant

0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.

Input Resolution:

Always four times better than display resolution. 16 bit ADC.

Supply Voltage
Influence:

Negligible effect on readings.

Relative Humidity
Influence:

Negligible effect on readings.

Temperature
Stability:

0.01% of span/C change in ambient temperature.

V DC:

47KΩ

mA DC:

Input Impedance:

Other ranges:

Greater than 10M resistive

Isolation:

Isolated from all outputs (except SSR Drivers) at 240V AC

PV Offset:

Adjustable input span. +ve values are added to Process Variable, -ve
values are subtracted from Process Variable

PV Display:

Displays process variable up to 5% over and 5% under span.

Thermocouple Input

Thermocouple Types & Ranges

Sensor
Type

Range in C

Range in F

Sensor
Type

Range in C

Range in F

B

100 to 1824°C

211 to 3315°F

L

0 to 762°C

32 to °F

C

0 to 2315°C

32 to 4199°F

N

0 to 1399°C

32 to 2551°F

D

0 to 2320°C

32 to 4208°F

PtRh20%:
PtRh40%

0 to 1850°C

32 to 3362°F

E

-240 to 1000°C

-400 to 1832°F

R

0 to 1759°C

32 to 3198°F

J (default) -200 to 1200°C

-328 to 2192°F

S

0 to 1762°C

32 to 3204°F

K

-240 to 1373°C

-400 to 2503°F

T

-240 to 400°C

-400 to 752°F

Note:

Defaults to °F for USA units. Defaults to °C for non-USA units.
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to
restrict range. An optional decimal place can be displayed up to 999.9°C/F